Real-time tracking and identification of Thevenin equivalent parameters is crucial for voltage stability online monitoring of large power grids. An online parameter identification method based on wide-area measurements and nodal analysis is proposed in this paper. The node-voltage equation is utilized directly, and the open-circuit voltage is calculated accurately as the Thevenin equivalent voltage of load buses. Moreover, the equivalent parameters can be identified precisely under the generator reactive power over-limit condition. To avoid repetitive Gaussian elimination of the high-dimensional linear system, lower upper factorization and optimized substitution are used to accelerate the open-circuit voltage solution process. The simulation results of multiple test systems demonstrate the accuracy and rapidity of the proposed method.
机译:戴维南等效参数的实时跟踪和识别对于大型电网的电压稳定性在线监测至关重要。提出了一种基于广域测量和节点分析的在线参数辨识方法。直接使用节点电压方程式,并准确计算开路电压作为负载母线的戴维南等效电压。此外,可以在发电机无功功率超限条件下精确识别等效参数。为避免高斯线性系统的重复高斯消除,使用较低的上因式分解和优化替代来加速开路电压解决方案的过程。多个测试系统的仿真结果证明了该方法的准确性和快速性。