首页> 外文期刊>IEEE Transactions on Power Delivery >Voltage distribution characteristics of series connected SF/sub 6/ gas and vacuum interrupters immediately after a large AC current interruption
【24h】

Voltage distribution characteristics of series connected SF/sub 6/ gas and vacuum interrupters immediately after a large AC current interruption

机译:交流电流大中断后,串联的SF / sub 6 /气体和真空断路器的串联电压分布特性

获取原文
获取原文并翻译 | 示例
           

摘要

Transient voltage distribution characteristics of a hybrid interrupter module have been examined using an experimental model of a hybrid breaker. Tests were conducted to study the voltage distribution between the SF/sub 6/ gas and the vacuum interrupters immediately after a long current interruption. It is found that the voltage distribution is determined by the resistive impedances of respective interrupters during the post arc current flow and by the capacitive impedances of the interrupter's contact gaps after the post arc current diminishes.
机译:已使用混合断路器的实验模型检查了混合断路器模块的瞬态电压分布特性。进行测试以研究在长电流中断后,SF / sub 6 /气体和真空断路器之间的电压分布。可以发现,电压分布是由弧后电流流动期间各个灭弧室的电阻阻抗和弧后电流减小后灭弧室接触间隙的电容阻抗确定的。