Increasing of ground resistance of human foot in substations' yards

机译:变电站场内人脚接地电阻的增加

获取原文
获取原文并翻译 | 示例
           

摘要

In a substation switchyard use of a plastic sheet immediately below the layer of crushed rock or the cement concrete pathway is proposed at locations where a high value of the grounding resistance of the human foot is required. A method to evaluate the grounding resistance of the foot when the plastic sheet is used is given. A procedure to estimate the reduction in the grounding resistance of the foot caused by a hole in the plastic sheet is proposed. The results have also been obtained through scale model studies. They compare favorably with the results obtained through the method proposed. Comparison of the touch potential with and without the plastic sheet is presented.
机译:在变电站开关站中,建议在需要高人脚接地电阻的位置使用碎石层或水泥混凝土通道下方的塑料板。给出了一种在使用塑料片时评估脚的接地电阻的方法。提出了一种估计由塑料板中的孔引起的脚的接地电阻的减小的过程。通过比例模型研究也获得了结果。它们与通过所提出的方法获得的结果相比具有优势。对比了使用和不使用塑料板时的触摸电位。