首页> 外文期刊>IEEE Transactions on Power Delivery >Ground resistance of the foot in substation yards
【24h】

Ground resistance of the foot in substation yards

机译:变电站内脚的接地电阻

获取原文
获取原文并翻译 | 示例
           

摘要

Equations and graphs given in IEEE Std 80 to determine ground resistance are not accurate and give conservative results. More accurate equations and graphs for determining the ground resistance of the human foot in a substation with a thin surface layer of gravel are given. An analysis has been made for models of the foot. In one model the foot is represented by an equivalent circular plate and in the other by an equivalent rectangular plate. Results obtained with these two models and with the IEEE Std 80 method are compared.
机译:IEEE Std 80中提供的用于确定接地电阻的方程式和图形不准确,并且给出的保守结果。给出了用于确定具有砾石薄层的变电站中人脚的接地电阻的更精确的方程式和图表。已经对脚的模型进行了分析。在一个模型中,脚由等效的圆形板表示,而在另一个模型中,由等效的矩形板表示。比较了使用这两种模型以及使用IEEE Std 80方法获得的结果。