Ferroresonant overvoltages in grounded wye-wye padmount transformers with low-loss silicon steel cores

机译:带低损耗硅钢芯的接地型Y型Y型Y型Y型Y型垫片式变压器中的铁磁过电压

获取原文
获取原文并翻译 | 示例
           

摘要

Reduced no-load losses have resulted in increased susceptibility to ferroresonance of grounded wye-wye three-phase distribution transformers using five-leg silicon steel wound cores. The authors describe the results of an extensive test program which determined that overvoltages are directly related to the ratio of capacitive susceptance divided by core losses and that the conventional use of rated exciting current can be a misleading indicator of ferroresonance susceptibility.
机译:减少的空载损耗导致使用五脚硅钢绕线铁芯的接地型W型-Y型三相配电变压器对铁磁谐振的敏感性增加。作者描述了一个广泛测试程序的结果,该程序确定过电压与容性电纳之比除以磁芯损耗直接相关,并且额定励磁电流的常规使用可能会误导铁磁谐振性。