首页> 外文期刊>IEEE Transactions on Power Delivery >Study of the acceptable DC current limit in core-form power transformers
【24h】

Study of the acceptable DC current limit in core-form power transformers

机译:研究铁心形式电力变压器中可接受的直流电流极限

获取原文
获取原文并翻译 | 示例
           

摘要

The temperature rise in power transformers subjected to a DC source of excitation was measured on core-form single-phase 735 kV autotransformers rated 370 MVA and 550 MVA. The measurements were compared to the temperature rise values obtained on the same transformers operating in overexcitation at 1.95 T. The results show that the tie plates of this particular type of transformer are the components most susceptible to rapid temperature rise. Smaller-scale tests on 100 kVA transformers were performed to take a specific look at these tie plates under the effect of a temperature increase. Finite-element simulations combined with analytical studies of temperature rise were performed in an attempt to determine a tolerable DC current limit based on permissible temperature standards.
机译:在额定功率为370 MVA和550 MVA的铁芯形式单相735 kV自耦变压器上测量了经受直流励磁电源的电力变压器的温升。将测量结果与在1.95 T过励磁的同一台变压器上获得的温升值进行比较。结果表明,这种特定类型的变压器的连接板是最容易快速温升的组件。在100 kVA变压器上进行了较小规模的测试,以便在温度升高的影响下对这些连接板进行具体观察。进行了有限元模拟与温度升高的分析研究相结合,以试图根据允许的温度标准确定可容忍的直流电流极限。