Improvement of operation of power transformer protection system during sympathetic inrush current phenomena using fault current limiter

机译:利用故障限流器改善在发生同感涌流现象时电力变压器保护系统的运行

获取原文
获取原文并翻译 | 示例
       

摘要

Power transformer protection has a high sensitivity due to its important role in power systems. Various factors such as inrush and sympathetic inrush currents may result in the inappropriate performance of protective relays and cause problems such as power outage or blocking of sensitive loads. Until now, several studies have been performed on the detection and reduction of inrush current, however, the effect of sympathetic inrush current on transformer protection has not been addressed. In this study, the operation of the protection system during the sympathetic inrush current is comprehensively analysed. Furthermore, the use of a fault current limiter is proposed to reduce the undesirable effects of the phenomena. The effects of the limiter on the saturation of power and current transformers are investigated. A real transmission station is simulated using DIgSILENT Power Factory Software to perform these studies by considering the resistive and impedance fault current limiter.‏ Results show that protective relays do not have an improper operation during the phenomena with limiters. Moreover, with the resistive fault current limiter, sympathetic inrush and inrush currents are decreased by 5 and 15% more than the impedance fault current limiter, respectively. Saturation of power and current transformers is significantly reduced with limiters, especially with a resistive fault current limiter.
机译:电力变压器保护由于其在电力系统中的重要作用而具有很高的灵敏度。各种因素(例如涌入和有同感的涌入电流)可能会导致保护继电器的性能不当,并引起诸如断电或敏感负载阻塞的问题。迄今为止,已经进行了一些有关检测和减小浪涌电流的研究,但是,尚未解决有同感的浪涌电流对变压器保护的影响。在这项研究中,对交感涌流中保护系统的运行进行了综合分析。此外,提出使用故障电流限制器以减少现象的不期望的影响。研究了限幅器对电源和电流互感器饱和的影响。通过考虑电阻性和阻抗故障限流器,使用DIgSILENT Power Factory软件对真实的传输站进行了仿真,以进行这些研究。结果表明,在出现限流器现象时,保护继电器不会发生不当操作。此外,使用电阻式故障电流限制器,同感涌流和涌入电流分别比阻抗故障电流限制器减少了5%和15%。使用限制器,尤其是使用电阻性故障电流限制器,可大大降低功率和电流互感器的饱和度。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号