Optimization of operating conditions of third harmonic ground-fault protection system of generator-transformer unit with two-states transverse parameters

机译:具有两个状态横向参数的发电机-变压器单元三次谐波接地保护系统的运行条件优化

获取原文
获取原文并翻译 | 示例
           

摘要

Such an optimization analysis of the operating conditions of the ground-fault protection excited by the third harmonic voltage for the two-state system of the generator-transformer unit transverse parameters is presented in this paper. The analysis was made for a unit in which a change in its transverse branch parameters occurs as a result of generator breaker switching operations. The optimization analysis has shown that effective ground-fault protection of the generator stator windings is possible, regardless of the operating conditions of the generator breaker.
机译:本文对发电机-变压器单元横向参数的二态系统中的三次谐波电压激励的接地保护的运行条件进行了优化分析。对一个单元进行了分析,该单元的横向分支参数由于发电机断路器的切换操作而发生了变化。优化分析表明,不管发电机断路器的工作条件如何,都可以对发电机定子绕组进行有效的接地保护。