Differences in Voltage Dip Exposure Depending Upon Phase-to-Phase and Phase-to-Neutral Monitoring Connections

机译:取决于相间和相间中性监控连接的浸入电压差异

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Voltage dip indices are estimated for a set of simulated and measured events. The simulated dips are obtained applying the method of fault positions on a large transmission network and the measured dips come from a one-year survey. The indices estimated to compare phase-to-phase and phase-to-neutral dips are SARFI-90, SARFI-70, SARFI–ITIC, and average voltage dip amplitude. Furthermore, the results are analyzed in terms of the cumulative distribution frequency of the voltage dip amplitude. The comparison of phase-to-phase and phase-to-neutral indices indicates that, at transmission level, phase-to-neutral dips are more frequent and more severe than phase-to-phase ones. However, these differences are reduced at the load connection level, where the phase and line voltages show similar performance for the monitored system.
机译:为一组模拟和测量事件估算电压骤降指数。通过使用大型传输网络上的故障位置方法获得模拟的倾角,测得的倾角来自一年的调查。估计用来比较相间和相间中性骤降的指数是SARFI-90,SARFI-70,SARFI–ITIC和平均电压骤降幅度。此外,根据电压骤降幅度的累积分布频率来分析结果。相间和相间中性指数的比较表明,在传输水平上,相间中性突降比相间中性突降更频繁,更严重。但是,这些差异在负载连接级别上有所减小,在负载连接级别上,相电压和线路电压对于受监控系统显示出相似的性能。