首页> 外文期刊>IEEE Transactions on Power Delivery >The Moisture in SF $_{6}$ Insulated CTs Considering Current and Change of Ambient Temperature
【24h】

The Moisture in SF $_{6}$ Insulated CTs Considering Current and Change of Ambient Temperature

机译:考虑电流和环境温度变化的SF $ _ {6} $绝缘CT中的水分

获取原文
获取原文并翻译 | 示例
           

摘要

SF$_{6}$ insulated current transformers (CTs) are widely used in high-voltage power systems due to their favorable insulating properties. Field experience shows that the high moisture content in an SF$_{6}$ -insulated CT is an important factor responsible for its insulation faults. Furthermore, the moisture content in an SF $_{6}$-insulated system is generally dependent on the ambient temperature. Thus, in this paper, the temperature distribution and moisture content of an SF$_{6}$ -insulated CT are studied by considering current flowing through it and a sharp change in the ambient temperature. It is found that the temperature distribution of an SF$_{6}$ -insulated CT in operation is extremely uneven, and the measured moisture content becomes higher than the initial moisture content. The relative humidity in the lower part of the CT might reach a dangerous level when the ambient temperature changes rapidly. The mechanism of moisture condensation is proposed to explain the experimental results. Besides, the possible preventive measures for insulation failure are also discussed.
机译:SF $ _ {6} $绝缘电流互感器(CT)由于其良好的绝缘性能而被广泛用于高压电力系统中。现场经验表明,SF $ _ {6} $绝缘CT中的高水分含量是造成绝缘故障的重要因素。此外,SF $ _ {6} $绝缘系统中的水分含量通常取决于环境温度。因此,在本文中,通过考虑流经SF $ _ {6} $的CT的电流分布和环境温度的急剧变化,研究了温度分布和水分含量。发现在运行中SF $ _ {6} $绝缘的CT的温度分布非常不均匀,并且测得的水分含量变得高于初始水分含量。当环境温度快速变化时,CT下部的相对湿度可能会达到危险水平。提出了水分凝结的机理来解释实验结果。此外,还讨论了防止绝缘故障的可能措施。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号