首页> 外文期刊>Plant engineering >Recognize a false negative in HiPot testing
【24h】

Recognize a false negative in HiPot testing

机译:识别HiPot测试中的假阴性

获取原文
获取原文并翻译 | 示例
           

摘要

A West Texas utility company received an alarm on one of its load tap changers. Field technicians found that one of the vacuum interrupters failed an ac high potential test. The tap changer was disassembled and the vacuum interrupter in question was tested again. Once removed, the vacuum interrupter passed an ac high potential test. The vacuum interrupter was reinstalled and placed back into service where it again passed an ac high potential test. The following explains why this utility company may have placed a failed vacuum interrupter back into service.
机译:一家西得克萨斯州的公用事业公司收到有关其中一个分接开关的警报。现场技术人员发现,其中一个真空灭弧室没有通过交流高电位测试。拆卸了分接开关,并再次测试了所涉及的真空开关管。拆除后,真空灭弧室通过了交流高电势测试。重新安装了真空灭弧室,使其重新投入使用,并再次通过了交流高电势测试。以下说明了为什么该公用事业公司可能将发生故障的真空灭弧室重新投入使用。