TRANSIENT STABILITY INVESTIGATION ON SINGLE POLE TRIPPING SCHEME OF THE 230 KV TRANSMISSION LINE IN NAM NGUM 2 HYDRO POWER PROJECT

机译:楠格姆2水电站230 kV输电线路单杆跳闸方案的暂态稳定研究。

获取原文
获取原文并翻译 | 示例
       

摘要

This paper presents the investigation on single pole tripping scheme of Nam Ngum 2 hydro power plant. The objective is to investigate and perform the simulation on the fault event which cause the generator instability and tripped from the system even though the transmission line between Nam Ngum 2 power plant and main grid was implemented with single-pole tripping scheme. The ATP-EMTP program has been used to conduct the transient stability study and modelling. The detailed model of hydro turbine governor, automatic voltage regulator (AVR), generator, transformer and transmission line are included in the simulation. The simulation result is presented and the comparison is made between the actual waveform which was recorded during the event and the simulated waveform to confirm the validity of the simulation model. The simulation result shown that the single-pole tripping could not help the generator to maintain the stability in this case. In addition, the model can be used to perform the parameters tuning for the better performance of the protection system.
机译:本文介绍了Nam Ngum 2水电厂的单极跳闸方案。目的是对故障事件进行调查并进行仿真,即使使用Nam Ngum 2电厂与主电网之间的传输线采用单极跳闸方案,也会导致发电机不稳定并从系统跳闸。 ATP-EMTP程序已用于进行暂态稳定性研究和建模。仿真中包括水轮机调速器,自动电压调节器(AVR),发电机,变压器和输电线路的详细模型。给出仿真结果,并比较事件期间记录的实际波形和仿真波形,以确认仿真模型的有效性。仿真结果表明,在这种情况下,单极跳闸不能帮助发电机保持稳定性。此外,该模型可用于执行参数调整,以实现更好的保护系统性能。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号