Heat transfer surface fouling introduces a major uncertainty into the design and operation of cooling water systems. Fouling caused by calcium carbonate (CaCO_3) typically occurs on heat transfer surfaces. Ozone has been successfully used for more than 90 years as a disinfectant in drinking water. Recently, it has been proposed to use ozone for cooling tower water treatment: In this research, the effectiveness of mitigation of calcium carbonate paniculate fouling by ozone was studied systematically. The experimental results show that, at low Reynolds numbers, though the ozonation retards the initial calcium carbonate paniculate fouling rate, the retardation led to a non-porous deposit layer and a higher asymptotic fouling resistance. However, at high Reynolds numbers, ozonation was found to reduce the asymptotic fouling resistance.
机译:传热表面结垢给冷却水系统的设计和运行带来了很大的不确定性。由碳酸钙(CaCO_3)引起的结垢通常发生在传热表面上。臭氧已成功用作饮用水消毒剂超过90年。最近,有人提出将臭氧用于冷却塔水处理:在这项研究中,系统地研究了臭氧减轻碳酸钙颗粒结垢的效果。实验结果表明,在低雷诺数下,虽然臭氧化作用会延迟最初的碳酸钙颗粒结垢率,但延迟会导致无孔沉积层和更高的渐近结垢阻力。然而,在高雷诺数下,发现臭氧化作用降低了渐近结垢阻力。