首页> 外文期刊>Journal of Heat Transfer >Extension of the Concepts of Heat Capacity Rate Ratio and Effectiveness-Number of Transfer Units Model to the Coupled Heat and Moisture Exchange in Liquid-to-Air Membrane Energy Exchangers
【24h】

Extension of the Concepts of Heat Capacity Rate Ratio and Effectiveness-Number of Transfer Units Model to the Coupled Heat and Moisture Exchange in Liquid-to-Air Membrane Energy Exchangers

机译:将热容量率比和传递单元的有效性数模型的概念扩展到液空膜交换器中的热湿耦合耦合

获取原文
获取原文并翻译 | 示例
       

摘要

The underlying concept of the standard effectiveness-number of transfer units (NTU) model is that the effectiveness of an exchanger can be correlated to two dimensionless parameters, namely, heat capacity ratio (Cr) and NTU. However, a limitation of this model is that it cannot account for the changes in effectiveness due to changes in operating temperature and humidity of simultaneous heat and moisture exchangers, specifically liquid-to-air membrane energy exchangers (LAMEEs). The purpose of this paper is to explain the reason for this limitation and also to explore the extension of the aforementioned concept of the effectiveness-NTU model to LAMEEs. The first contribution of this paper is to demonstrate that the reason for this limitation is that one of the simplifying assumptions of the standard effectiveness-NTU model, i.e., that Cr represents the ratio between the changes in the temperatures of the two fluid streams across an exchanger, is not applicable to LAMEEs. Further analysis in this paper yields two new fundamental dimensionless parameters that are analogous to Cr, termed effective Cr and effective m~*, which represent the actual ratios between the changes in the temperatures and humidity ratios of the fluid streams. Then, it is shown that models analogous to the standard effectiveness-NTU model can be used to correlate the dependency of the effectiveness of LAMEEs on the operating temperature and humidity to effective Cr and effective m~*.
机译:标准效率-转移单位数量(NTU)模型的基本概念是,交换器的有效性可以与两个无量纲参数相关,即热容比(Cr)和NTU。但是,该模型的局限性在于,它不能解决由于同时进行的热和湿气交换器(特别是液-气膜能量交换器(LAMEE))的工作温度和湿度变化而导致的效率变化。本文的目的是解释这种局限性的原因,并探讨将有效性NTU模型的上述概念扩展到LAMEE。本文的第一个贡献是证明了这种局限性的原因是标准有效性-NTU模型的简化假设之一,即Cr代表了两个流体流的温度变化之间的比率。交换器,不适用于LAMEE。本文的进一步分析得出了两个类似于Cr的基本无量纲参数,称为有效Cr和有效m〜*,它们代表了流体温度和湿度比率变化之间的实际比率。然后,表明可以使用类似于标准有效性-NTU模型的模型来将LAMEE的有效性对工作温度和湿度的依赖性与有效Cr和有效m〜*相关联。

著录项

  • 来源
    《Journal of Heat Transfer》 |2016年第9期|092001.1-092001.12|共12页
  • 作者单位

    Department of Mechanical Engineering, University of Saskatchewan, 57 Campus Drive, Saskatoon, SK S7N 5A9, Canada;

    Department of Mechanical Engineering, University of Saskatchewan, 57 Campus Drive, Saskatoon, SK S7N 5A9, Canada;

    Department of Mechanical Engineering, University of Saskatchewan, 57 Campus Drive, Saskatoon, SK S7N 5A9, Canada;

    Department of Mechanical Engineering, University of Saskatchewan, 57 Campus Drive, Saskatoon, SK S7N 5A9, Canada;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);