首页> 外文期刊>Journal of Heat Transfer >High Performance Loop Heat Pipe With Flat Evaporator for Energy-Saving Cooling Systems of Supercomputers
【24h】

High Performance Loop Heat Pipe With Flat Evaporator for Energy-Saving Cooling Systems of Supercomputers

机译:超级计算机节能冷却系统的带平面蒸发器的高性能环路热管

获取原文
获取原文并翻译 | 示例
       

摘要

Two high performance loop heat pipes (LHPs) are developed for direct cooling of the chips in supercomputer. The two LHPs using flat evaporator are: one called water-cooling LHP and another one called air-cooling LHP. The working fluid of LHP is ammonia. The water-cooling LHP can work well at a heat load up to 663 W and air-cooling LHP can work well at a heat load up to 513 W. The two LHPs applying to the real computer servers are realized and tested. The server test results with water-cooling LHP have shown that the operating temperature of central processing units (CPUs) can be controlled to about 67 ℃ to ensure the reliable operating and acceptable level for electronic chips, even at condenser-cooling water temperature of 40℃ with low water flowrate of 0.055 m~3/h. The server test results with air-cooling LHP have shown that the operating temperature of CPUs can be controlled to about 51 ℃ even at condenser-cooling wind temperature of 30℃ with wind flowrate of 41.88 m~3 /h.
机译:开发了两个高性能回路热管(LHP),用于直接冷却超级计算机中的芯片。使用平面蒸发器的两种LHP是:一种称为水冷LHP,另一种称为空冷LHP。 LHP的工作流体是氨。水冷LHP在高达663 W的热负荷下可以很好地工作,而风冷LHP在高达513 W的热负荷下可以很好的工作。这两个应用于真实计算机服务器的LHP均已实现并经过测试。使用水冷LHP的服务器测试结果表明,即使在冷凝器冷却水温度为40℃时,中央处理器(CPU)的工作温度也可以控制在67℃左右,以确保电子芯片的可靠工作和可接受的水平。 ℃,低水流量0.055 m〜3 / h。空冷LHP的服务器测试结果表明,即使在冷凝器冷却风温度为30℃,风量为41.88 m〜3 / h的情况下,CPU的工作温度也可以控制在51℃左右。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号