Full-scale depressurization of a section of a riser platform. Measurements and comparison with simulations

机译:对立管平台的一部分进行全面降压。测量和与模拟的比较

获取原文
获取原文并翻译 | 示例
           

摘要

Full-scale depressurization tests have been carried out on a riser platform in order to measure outer surface temperatures in the depressurized section of the platform. The tests are performed primarily to find out if the occurring steel temperatures are acceptable during depressurization, and secondly to obtain full-scale experimental data for comparison with the simulation code PIA. Blow-down from two initial pressure levels were tested, 88 and 70 bar. The test section volume was depressurized through a 25 mm nozzle and a pressure of 8 bar was obtained after about 11 and 9 min, respectively. The results of the measurements show that the maximum surface temperature drop is about 9℃ at an initial pressure of 88 bar and 6℃ at an initial pressure of 70 bar. The lowest outer surface temperature registered was -4℃. The depressurization tests were also simulated using the finite difference code PIA, and the results for outer wall temperatures are in close agreement with the measurements. Comparisons between heat transfer coefficients used in the simulation code and estimated heat transfer coefficients from the measurements are also in good agreement.
机译:为了测量平台降压段的外表面温度,已经在立管平台上进行了全面的降压测试。进行测试主要是为了找出降压过程中出现的钢水温度是否可以接受,其次是获得全面的实验数据以与模拟代码PIA进行比较。测试了两个初始压力水平(88和70 bar)的排放。通过25mm喷嘴对测试部分的体积减压,分别在约11分钟和9分钟后获得8巴的压力。测量结果表明,在88 bar的初始压力下最大表面温度下降约9℃,在70 bar的初始压力下最大表面温度下降6℃。记录的最低外表面温度为-4℃。还使用有限差分代码PIA对降压测试进行了模拟,并且外壁温度的结果与测量结果非常吻合。模拟代码中使用的传热系数与根据测量结果估算的传热系数之间的比较也很一致。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号