Experimentally Validated Computational Fluid Dynamics Model for Data Center With Active Tiles

机译:具有活动磁贴的数据中心的实验验证计算流体动力学模型

获取原文
获取原文并翻译 | 示例
           

摘要

This paper presents an experimentally validated room-level computational fluid dynamics (CFD) model for raised-floor data center configurations employing active tiles. Active tiles are perforated floor tiles with integrated fans, which increase the local volume flow rate by redistributing the cold air supplied by the computer room air conditioning (CRAC) unit to the under-floor plenum. The numerical model of the data center room consists of one cold aisle with 12 racks arranged on both sides and three CRAC units sited around the periphery of the room. The commercial CFD software package future facilities 6sigmadcx is used to develop the model for three configurations: (a) an aisle populated with ten (i.e., all) passive tiles; (b) a single active tile and nine passive tiles in the cold aisle; and (c) an aisle populated with all active tiles. The predictions from the CFD model are found to be in good agreement with the experimental data, with an average discrepancy between the measured and computed values for total flow rate and rack inlet temperature less than 4% and 1.7 °C, respectively. The validated models were then used to simulate steady-state and transient scenarios following cooling failure. This physics-based and experimentally validated room-level model can be used for temperature and flow distributions prediction and identifying optimal number and locations of active tiles for hot spot mitigation in data centers.
机译:本文介绍了一种经过实验验证的,采用活动瓦片的高架数据中心配置的房间级计算流体动力学(CFD)模型。活动地板砖是带有集成风扇的多孔地板砖,通过将计算机机房空调(CRAC)单元提供的冷空气重新分配到地板下通风系统,从而增加了局部体积流量。数据中心机房的数值模型由一个冷通道和左右两侧的三个CRAC单元组成,冷通道的两侧各有12个机架。商业CFD软件包的未来设施6sigmadcx用于开发三种配置的模型:(a)装有十个(即所有)无源砖的过道; (b)冷通道中有一个有源砖和九个无源砖; (c)摆满所有活动瓷砖的过道。 CFD模型的预测与实验数据非常吻合,总流量和机架入口温度的测量值与计算值之间的平均差异分别小于4%和1.7C。然后将经过验证的模型用于模拟冷却故障后的稳态和瞬态情况。这种基于物理学的,经过实验验证的房间级模型可用于预测温度和流量分布,并确定用于缓解数据中心热点的活动砖的最佳数量和位置。

著录项

  • 来源
    《Journal of Electronic Packaging》 |2018年第1期|010902.1-010902.10|共10页
  • 作者单位

    George W. Woodruff School ofMechanical Engineering,Georgia Institute of Technology,Atlanta, GA 30332;

    George W. Woodruff School ofMechanical Engineering,Georgia Institute of Technology,Atlanta, GA 30332;

    George W. Woodruff School ofMechanical Engineering,Georgia Institute of Technology,Atlanta, GA 30332;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Tiles; Data centers; Flow (Dynamics); Temperature;

    机译:磁贴;数据中心;流(动态);温度;

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号