首页> 外文期刊>International Journal of Heat and Mass Transfer >Modeling of a flat plate membrane-distillation system for liquid desiccant regeneration in air-conditioning applications
【24h】

Modeling of a flat plate membrane-distillation system for liquid desiccant regeneration in air-conditioning applications

机译:用于空调应用中的液体干燥剂再生的平板膜蒸馏系统的建模

获取原文
获取原文并翻译 | 示例
           

摘要

A thermally driven flat plate air gap membrane distillation liquid desiccant regenerator for lithium chloride in dehumidification applications is modeled. Operating conditions and device geometry are optimized, and it is found that membrane materials have little influence on regenerator performance. It is shown that radiation heat transfer across the air gap cannot be neglected. The regenerator removes 11.4 g min"1 cm"3 of moisture with a COP of 0.372 for an inlet solution concentration of 0.38, solution flow rate of 50 ml min"1, and heated solution temperature of 135 ℃. This design has negligible desiccant carry-over losses and operates without a blower.
机译:对用于除湿应用中氯化锂的热驱动平板气隙膜蒸馏液体干燥剂再生器进行了建模。优化了操作条件和设备的几何形状,发现膜材料对再生器性能的影响很小。结果表明,辐射热在气隙中的传递不能忽略。对于进口溶液浓度为0.38,溶液流速为50 ml min“ 1和加热溶液温度为135℃,再生器可去除11.4 g min” 1 cm“ 3的水分,COP为0.372。该设计的干燥剂携带量可忽略不计-损耗大,无需鼓风机即可运行。