Experimental comparative research on electrodialysis regeneration for liquid desiccant with different concentrations in liquid desiccant air-conditioning system

机译:液体干燥剂空调系统中不同浓度液体干燥剂电渗析再生的实验对比研究

获取原文
获取原文并翻译 | 示例
       

摘要

The issue of energy and environment is increasingly prominent, and air-conditioning system costs a lot of energy in the building. The liquid desiccant air-conditioning system is a novel air-conditioner with good energy saving potential, whose energy consumption mainly relies on the regeneration process of liquid desiccant. In this paper, an experimental system of electrodialysis (ED) regenerator was set up to confirm the stability of the ED regenerator for the regeneration of liquid desiccant with different concentrations and the regeneration performance of the ED regenerator for liquid desiccant with different concentrations was investigated. Moreover, the ideal COP of the liquid desiccant air-conditioning system and vapor pressure of the acquired strong desiccant at the exit of the ED regenerator were also evaluated to compare the characteristic of the ED regenerator for liquid desiccant with different concentrations. The result shows that besides high concentration, the low temperature is also very important for liquid desiccant to have high dehumidification capacity. Moreover, the excessive increase of current will be more harmful to the dehumidification capacity of the acquired strong liquid desiccant when liquid desiccant concentration is around 35%. Furthermore, when liquid desiccant concentration is around 35%, the ED regenerator needs more power to achieve liquid desiccant with the same dehumidification capacity. (C) 2017 Elsevier B.V. All rights reserved.
机译:能源和环境问题日益突出,空调系统在建筑物中消耗大量能源。液体干燥剂空调系统是一种具有良好节能潜力的新型空调,其能耗主要取决于液体干燥剂的再生过程。本文建立了电渗析(ED)再生器实验系统,以确认ED再生器对不同浓度的液体干燥剂再生的稳定性,并研究了ED再生器对不同浓度的液体干燥剂的再生性能。此外,还评估了液体干燥剂空调系统的理想COP和在ED再生器出口处获得的强干燥剂的蒸气压,以比较ED再生器对于不同浓度的液体干燥剂的特性。结果表明,除高浓度外,低温对于具有高除湿能力的液体干燥剂也很重要。此外,当液体干燥剂浓度为约35%时,电流的过度增加将对所获得的强液体干燥剂的除湿能力更加有害。此外,当液体干燥剂的浓度约为35%时,ED再生器需要更多的功率来实现具有相同除湿能力的液体干燥剂。 (C)2017 Elsevier B.V.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号