As electronics packages become increasingly thinner and more compact due to size, weight, and performance demands, the use of large intermediate heat spreaders to mitigate heat generation non-uniformities are no longer a viable option. Instead, non-uniform heat flux profiles produced from chip-scale variations or from multiple discrete devices are experienced directly by the ultimate heat sink. In order to address these thermal packaging trends, a better understanding of the impacts of non-uniform heating on two-phase flow characteristics and thermal performance limits for microchannel heat sinks is needed. An experimental investigation is performed to explore flow boiling phenomena in a microchannel heat sink with hotspots, as well as non-uniform streamwise and transverse peak-heating conditions spanning across the entire heat sink area. The investigation is conducted using a silicon microchannel heat sink with a 5 × 5 array of individually controllable heaters attached to a 12.7 mm × 12.7 mm square base. The channels are 240 μm wide, 370 μm deep, and separated by 110 μm wide fins. The working fluid is the dielectric fluorinert liquid FC-77, flowing at a mass flux of approximately 890 kg/m~2 s. High-speed visualizations of the flow are recorded to observe the local flow regimes. Despite the substrate beneath the microchannels being very thin (200 μm), significant lateral conduction occurs and must be accounted for in the calculation of the local heat flux imposed. For non-uniform heat input profiles, with peak heat fluxes along the streamwise and transverse directions, it is found that the local flow regimes, heat transfer coefficients, and wall temperatures deviate significantly from a uniformly heated case. These trends are assessed as a function of an increase in the relative magnitude of the nonuniformity between the peak and background heat fluxes.
机译:随着电子封装由于尺寸,重量和性能要求而变得越来越薄和紧凑,使用大型中间散热器来减轻热量产生的不均匀性不再是可行的选择。取而代之的是,最终的散热器会直接经历由芯片尺寸变化或多个分立器件产生的不均匀热通量曲线。为了解决这些热包装趋势,需要更好地理解非均匀加热对两相流特性的影响以及微通道散热器的热性能极限。进行了一项实验研究,以探讨具有热点的微通道散热器中的沸腾现象,以及横跨整个散热器区域的不均匀的沿流向和横向的峰值加热条件。使用硅微通道散热器进行研究,该散热器具有5×5阵列的可独立控制的加热器,该加热器连接到12.7 mm×12.7 mm的方形底座上。通道宽240μm,深370μm,并由110μm宽的鳍片隔开。工作流体是电介质氟化物液体FC-77,以约890 kg / m〜2 s的质量通量流动。记录流动的高速可视化以观察局部流动状况。尽管微通道下面的基板非常薄(200μm),但仍会发生明显的横向传导,必须在计算施加的局部热通量时加以考虑。对于非均匀的热输入曲线,沿流向和横向具有峰值热通量,发现局部流态,传热系数和壁温明显不同于均匀加热的情况。这些趋势被评估为峰值和背景热通量之间不均匀性的相对幅度增加的函数。

著录项

  • 来源
  • 作者单位

    Cooling Technologies Research Center, an NSF I/UCRC, School of Mechanical Engineering, Purdue University, 585 Purdue Mall, West Lafayette, IN 47907, USA;

    Cooling Technologies Research Center, an NSF I/UCRC, School of Mechanical Engineering, Purdue University, 585 Purdue Mall, West Lafayette, IN 47907, USA;

    Cooling Technologies Research Center, an NSF I/UCRC, School of Mechanical Engineering, Purdue University, 585 Purdue Mall, West Lafayette, IN 47907, USA;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Non-uniform heating; Hot spot; MicroChannel heat sink; Two-phase flow; Boiling;