首页> 外文期刊>International Journal of Heat and Mass Transfer >Air pre-heating for anti-freezing of air-cooled heat exchanger by spraying flue gas
【24h】

Air pre-heating for anti-freezing of air-cooled heat exchanger by spraying flue gas

机译:通过喷涂烟道气来预热预热,用于通过喷涂烟道气体防冻热交换器

获取原文
获取原文并翻译 | 示例
           

摘要

In cold winter, natural draft dry cooling system (NDDCS) confronts a severe freezing risk due to high cooling capacity of ambient air. In this work, the anti-freezing of air-cooled heat exchanger by spraying flue gas at the inlet of cooling deltas to pre-heat ambient air is proposed. With the coupled heat transfer models of steam condenser and NDDCS, the cooling performance of air-cooled heat exchanger and the minimum outlet water temperatures of various sectors are obtained at three typical low ambient temperatures, based on which the flue gas spraying strategies for the potential frozen sectors are analyzed. At not very low ambient temperature of 268.15 K, the flue gas should be sprayed for the frontal and middle front sectors at the wind speeds of 8 m/s and 12 m/s. At 263.15 K, the frozen sectors differ greatly as the wind speed increases, besides some non-frozen sectors should also be pre-heated. As the ambient temperature drops to 258.15 K, more flue gas should be sprayed at all wind speeds due to the increased air cooling capacity. By spraying flue gas, the pre-heated air can contribute to the safe and energy efficient operation of NDDCS in frozen days. (C) 2019 Elsevier Ltd. All rights reserved.
机译:在寒冷的冬季,由于环境空气的高冷却能力,天然干燥冷却系统(NDDCS)对抗严重的冻结风险。在这项工作中,提出了通过在冷却Δ的入口处喷射烟道气来预热环境空气的烟气冷却热交换器的防冻。利用蒸汽冷凝器和NDDC的耦合传热模型,在三个典型的低环境温度下获得空气冷却热交换器的冷却性能和各个部门的最小出口水温,基于该局部烟气喷射策略冻结部门分析。在268.15 k的环境温度不是非常低的情况下,应在8 m / s和12米/秒的风速下喷涂烟道气。在263.15 k时,随着风速增加,冰冻扇区的差异很大,除了一些非冻结的部门,还应预先加热。随着环境温度下降至258.15 k,由于增加的空气冷却能力增加,应在所有风速下喷洒更多的烟气。通过喷射烟道气,预热空气可以有助于冷冻天中NDDC的安全和节能。 (c)2019 Elsevier Ltd.保留所有权利。

著录项

  • 来源
  • 作者单位

    North China Elect Power Univ Sch Energy Power & Mech Engn Minist Educ Key Lab Condit Monitoring & Control Power Plant E Beijing 102206 Peoples R China;

    North China Elect Power Univ Sch Energy Power & Mech Engn Minist Educ Key Lab Condit Monitoring & Control Power Plant E Beijing 102206 Peoples R China;

    North China Elect Power Univ Sch Energy Power & Mech Engn Minist Educ Key Lab Condit Monitoring & Control Power Plant E Beijing 102206 Peoples R China;

    North China Elect Power Univ Sch Energy Power & Mech Engn Minist Educ Key Lab Condit Monitoring & Control Power Plant E Beijing 102206 Peoples R China;

    North China Elect Power Univ Sch Energy Power & Mech Engn Minist Educ Key Lab Condit Monitoring & Control Power Plant E Beijing 102206 Peoples R China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Natural draft dry cooling system; Air-cooled heat exchanger; Flue gas spraying; Anti-freezing; Air pre-heating; Outlet water temperature;

    机译:天然吹风干燥冷却系统;风冷换热器;烟气喷涂;防冻;空气预热;出口水温;