The present study investigated the effect of two tube inserts (wire coil and wire mesh) on the heat transfer enhancement, pressure drop and mineral salts fouling mitigation in tube of a heat exchanger. A 3/4-in. tube that is heated by band heaters, is used which simulated a tube of heat exchanger. Working fluid is water with certain quality. The heat transfer rate averagely increased by 22-28% for wire coil (p/d=0.125, e/d=0.00375) and 163-174% for wire mesh (medium density) over a plain tube value, depending on type of tube insert, density of wire torsion and flow velocity. However, the pressure drop also increased substantially by 46% for wire coil and 500% for wire mesh. Wire coil insert with vibration mitigate mineral salts fouling (scaling) about 34%, and wire mesh have no effect on scaling, however it sometimes increased deposit rate.
机译:本研究研究了两个管插入物(线圈和丝网)对换热器管内传热增强,压降和矿物盐结垢缓解的影响。 3/4英寸用带式加热器加热的热管模拟了热交换器管。工作流体是一定质量的水。根据管子的类型,在普通管子上,线盘管的传热率平均提高22-28%(p / d = 0.125,e / d = 0.00375),而网孔的传热率平均提高163-174%(中等密度)插入量,线扭密度和流速。但是,金属丝线圈的压降也显着增加了46%,金属丝网的压降也增加了500%。带有振动的金属丝插入物可减轻约34%的矿物盐结垢(水垢),而金属丝网对水垢没有影响,但是有时会增加沉积速率。