Recent testing with various electrode configurations and insulating barriers suggests that 250-V equipment omitted from arc flash hazard analyses has the potential for burn injury. Research into the sustainability of arcs at these voltages shows that assumptions about the magnitude of these hazards need to be revised. This research enhanced the work of previous efforts by focusing on the sustainability of arcs with fault currents lower than 10 kA. Gap lengths between electrodes, electrode shape, electrode material, and voltage variations are studied for their effects on arc sustainability. A modified barrier design representative of the space around panelboard bus bars is also studied.
机译:最近对各种电极配置和绝缘屏障的测试表明,弧闪危险分析中省略的250 V设备可能会造成烧伤。对在这些电压下电弧可持续性的研究表明,关于这些危害的严重性的假设需要修改。这项研究的重点是故障电流低于10 kA的电弧的可持续性,从而增强了以前的工作。研究了电极之间的间隙长度,电极形状,电极材料和电压变化对电弧可持续性的影响。还研究了代表配电盘母线周围空间的改进型屏障设计。