首页> 外文期刊>Industrial Electronics, IEEE Transactions on >On the Stability of Local Voltage Control in Distribution Networks With a High Penetration of Inverter-Based Generation
【24h】

On the Stability of Local Voltage Control in Distribution Networks With a High Penetration of Inverter-Based Generation

机译:基于逆变器的高穿透率配电网局部电压控制的稳定性研究

获取原文
获取原文并翻译 | 示例
           

摘要

A stability study of distribution networks with a high penetration of distributed generators (DGs) actively supporting the network is presented in this paper. A possible way of mitigating the voltage rise caused by DGs is the local control of reactive power. Among the different possible options, the Q(U) control (reactive power as a function of the voltage) is one of the commonly suggested solutions. However, the Q(U) control can, under certain conditions, lead to instability. This paper summarizes the results of a stability study conducted on a single-inverter system and on a multiinverter system. It shows that the requirements for reaching a stable operation can easily be met for integrated systems but could be a significant constraint for systems relying on communication.
机译:本文提出了一种积极支持配电网的分布式发电系统,其中分布式发电系统(DG)具有较高的渗透率。缓解由DG引起的电压升高的一种可能方法是对无功功率进行本地控制。在不同的可能选项中,Q(U)控制(无功功率随电压的变化)是通常建议的解决方案之一。但是,在某些条件下,Q(U)控制会导致不稳定。本文总结了在单逆变器系统和多逆变器系统上进行的稳定性研究的结果。它表明,对于集成系统而言,达到稳定运行的要求很容易满足,但对于依赖通信的系统而言,这可能是一个重大约束。