Diagnosis by Acetone for Deterioration of Breathing Transformers Containing an Adsorbent in the Insulating Oil.

机译:通过丙酮诊断绝缘油中含有吸附剂的呼吸变压器劣化。

获取原文
获取原文并翻译 | 示例
           

摘要

Aging deterioration of transformers can be diagnosed by amounts of CO_2+CO and furfural decomposed from insulating papers. But, in case of breathing transformers containing an adsorbent in the insulating oil, CO_2 and CO gassesare exhausted through the breather and the furfural is almost adsorbed by the adsorbent. Therefore, in order to obtain the true values of each amount of CO_2+CO and furfural, some corrections for measured values are necessary.
机译:可以通过从绝缘纸上分解出的CO_2 + CO和糠醛来诊断变压器的老化。但是,如果呼吸变压器的绝缘油中含有吸附剂,则通气器会排出CO_2和CO气体,糠醛几乎被吸附剂吸附。因此,为了获得每个CO_2 + CO和糠醛的真实值,需要对测量值进行一些校正。