Location of the prebreakdown region in a cross-linked polyethylene insulated cable

机译:预击穿区域在交联聚乙烯绝缘电缆中的位置

获取原文
获取原文并翻译 | 示例
           

摘要

A method of locating discharges during breakdown tests on medium-voltage cables is described. The resistive screen of the cable attenuates the discharge pulses and the location is made by using the magnitude of the pulses recorded at each end of the cable, allowance must be made for pulse reflection. Tests on an 11 kV polyethylene insulated cable that contained large vented water trees are used to illustrate the method. Total discharge energy and location were recorded for a single discharging site. The test was stopped prior to breakdown and a volume of insulation containing a single electrical tree was cut from the cable. The computed discharge energy was compared with the eroded volume within the electrical tree.
机译:描述了一种在中压电缆的击穿测试过程中确定放电位置的方法。电缆的电阻屏会衰减放电脉冲,并通过使用记录在电缆两端的脉冲幅度来确定位置,必须留出脉冲反射空间。该方法通过对包含大型排水水树的11 kV聚乙烯绝缘电缆进行测试来说明。记录单个放电位置的总放电能量和位置。在击穿之前停止测试,并从电缆上切下包含单个电气树的绝缘层。将计算出的放电能量与电气树内的侵蚀体积进行比较。