摘要

Differential relays are the main protection for power transformers including transmission and industrial transformers. Protection against internal fault is generally relegated to these relays. The most probable internal fault of the industrial transformer is phase to ground type. To limit the fault current in this condition, a limiter resistor is utilised in the transformer. However, it has considerable impact on sensitivity of the differential and restricted earth fault (REF) protections. In this study, an effective approach is proposed to improve the differential and REF protections sensitivity of the industrial transformers. The proposed technique not only realises the fault current limitation function, but preserves sensitivity of the protections. In this method, a developed fault current limiter is utilised in the transformer neutral instead of the neutral grounding resistor. The performance of the proposed technique is evaluated by some simulations and experiments. The results confirm the high capability of the proposed technique in different conditions.
机译:差动继电器是包括传输和工业变压器在内的电力变压器的主要保护装置。防止内部故障的保护措施通常属于这些继电器。工业变压器最可能的内部故障是相接地类型。为了在这种情况下限制故障电流,在变压器中使用了一个限制器电阻。但是,它对差动和受限接地故障(REF)保护的灵敏度有很大影响。在这项研究中,提出了一种有效的方法来提高工业变压器的差动和REF保护灵敏度。所提出的技术不仅实现了故障电流限制功能,而且保持了保护的灵敏度。在这种方法中,在变压器中性点而不是中性点接地电阻器中使用了开发的故障电流限制器。通过一些仿真和实验评估了所提出技术的性能。结果证实了所提出的技术在不同条件下的高能力。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号