首页> 外文期刊>Electric power systems research >A wavelet-based restricted earth-fault power transformer differential protection
【24h】

A wavelet-based restricted earth-fault power transformer differential protection

机译:基于小波的限制接地故障电力变压器差动保护

获取原文
获取原文并翻译 | 示例
           

摘要

This paper proposes a restricted earth fault protection based on the wavelet transform (REFW) for detecting ground faults close to the transformer neutral point (turn-to-ground faults) and supporting the conventional phase differential protection, which presents limitations in this kind of faults. The proposed REFW protection uses only high-frequency components instead of phasor estimation, speeding up the detection of turn-to-ground faults. A performance comparison between the proposed wavelet-based restricted earth-fault differential protection and the respective conventional restricted earth-fault (REF) unit was accomplished considering simulated turn-to-ground faults, involving a few winding turns. The proposed method is more efficient and faster than the conventional one, reaching a success rate of 100%.
机译:本文提出了一种基于小波变换(REFW)的受限制的接地故障保护,用于检测接近变压器中性点(转向地故障)的接地故障并支持传统的相位差动保护,这呈现了这种故障的限制 。 所提出的REFW保护仅使用高频分量而不是相平衡估计,加快转向地故障的检测。 考虑模拟的转向地断层,完成了所提出的基于小波的受限接地故障差分保护和相应的传统限制接地故障(REF)单元之间的性能比较。 所提出的方法比传统的方法更高效,更快地达到100%的成功率。