首页> 外文期刊>Advances in Electrical and Computer Engineering >A New Method of Improving Transformer Restricted Earth Fault Protection
【24h】

A New Method of Improving Transformer Restricted Earth Fault Protection

机译:一种改善变压器限流接地保护的新方法

获取原文
           

摘要

A new method of avoiding malfunctioning of the transformer restricted earth fault (REF) protection is presented. Application of the proposed method would eliminate unnecessary operation of REF protection in the cases of faults outside protected zone of a transformer or a magnetizing inrush accompanied by current transformer (CT) saturation. On the basis of laboratory measurements and simulations the paper presents a detailed performance assessment of the proposed method which is based on digital phase comparator. The obtained results show that the new method was stable and precise for all tested faults and that its application would allow making a clear and precise difference between an internal fault and: (i) external fault or (ii) magnetizing inrush. The proposed method would improve performance of REF protection and reduce probability of maloperation due to CT saturation. The new method is robust and characterized by high speed of operation and high reliability and security.
机译:提出了一种避免变压器受限接地故障(REF)保护故障的新方法。如果在变压器的保护区域之外发生故障,或者励磁涌流伴随电流互感器(CT)饱和,则所提出方法的应用将消除不必要的REF保护操作。在实验室测量和仿真的基础上,本文对基于数字相位比较器的方法进行了详细的性能评估。所获得的结果表明,该新方法对于所有测试过的故障都是稳定且精确的,并且其应用将使内部故障与(i)外部故障或(ii)励磁涌流之间产生清晰而精确的区别。所提出的方法将改善REF保护的性能并减少由于CT饱和而引起的误操作的可能性。该新方法具有鲁棒性,并且具有操作速度快,可靠性和安全性高的特点。