The radiant cooling system generally operates with the dedicated outdoor air system (DOAS). Air supply modes and the corresponding setting parameters of the hybrid system may substantially influence the indoor thermal comfort. With target indexes of air diffusion performance index (ADPI) and predicted mean vote (PMV), the Taguchi method was used to choose the optimal air supply mode and to analyze the significance of different factors on the thermal comfort. The results are expected for conducting the future design and regulation of the hybrid system. Computation fluid dynamics (CFD) simulation as well as verified experiments was performed during the research. Based on the ADPI studies, it is found that the air supply mode of ceiling delivery with ceiling exhaust is an optimized option to apply in DOAS of the hybrid system. Variance analysis results show that influence fact of air supply temperature is the most dominant one to impact the indoor thermal comfort index of PMV.
机译:辐射冷却系统通常与专用室外空气系统(DOAS)一起运行。空气供应模式和混合动力系统的相应设置参数可能会严重影响室内的热舒适性。通过目标空气扩散性能指数(ADPI)和预测平均投票(PMV)指标,田口方法被用来选择最佳的空气供应模式,并分析了不同因素对热舒适性的重要性。预期结果将用于混合系统的未来设计和调节。在研究过程中进行了计算流体动力学(CFD)模拟以及经过验证的实验。根据ADPI的研究,发现带有天花板排气的天花板送风的供气模式是混合系统DOAS中应用的最佳选择。方差分析结果表明,送风温度的影响因素是影响PMV室内热舒适指数的最主要因素。