Expanded polystyrene (EPS) and extruded polystyrene (XPS) foams are both excellent exterior thermal insulation materials for buildings. However, their flammability also induces high fire hazard. Current regulation in China requires horizontal fire barriers with a minimum height of 30 cm when polystyrene foams are used as the external insulation. The present work evaluates the effectiveness of such barriers in inhibiting fire growth in insulation walls. The walls were made of B2 grade EPS and XPS foams without protective coatings but with mineral wool as horizontal barriers. Altogether six combinations of fire positions and barrier positions were tested for both EPS and XPS. The heat release rate (HRR) of the fire and the temperature distribution on the wall were recorded and analyzed. The results indicate that, without a barrier, fire starting at the middle of the wall generated higher peak HRR than that starting at the bottom, which was in turn higher than that starting at the top. When the insulation panel below the barrier was 1 m high, the upward fire spread from the bottom could be stopped by 40-cm, but not 30-cm, barriers. However, when the insulation panel below the barrier was 2 m high, even the 40-cm barriers failed. Lastly, the downward fire spread from above could not be stopped by 40-cm barrier due to dripping of burning plastics. The study highlights the limitations of horizontal fire barriers in preventing the vertical fire spread over exposed B2 grade polystyrene insulation and establishes protocols for further investigations.
机译:发泡聚苯乙烯(EPS)和挤出聚苯乙烯(XPS)泡沫都是建筑物的出色外部隔热材料。然而,它们的易燃性也引起着火的危险。中国目前的法规要求,当使用聚苯乙烯泡沫塑料作为外部隔热材料时,水平防火屏障的高度不得低于30厘米。本工作评估了这种屏障在抑制隔热墙内火灾增长方面的有效性。墙壁由B2级EPS和XPS泡沫制成,不带保护性涂层,但以矿棉为水平屏障。对EPS和XPS总共测试了六个着火位置和屏障位置的组合。记录并分析了火灾的热释放率(HRR)和墙壁上的温度分布。结果表明,在无障碍的情况下,始于墙中间的火灾产生的峰值HRR高于始于底部的峰值,进而高于始于顶部的峰值。当屏障下方的隔热板高1 m时,可以阻止40厘米而不是30厘米的屏障阻止从底部向上蔓延的火势。但是,当障碍物下方的隔热板高2 m时,即使40厘米的障碍物也无法使用。最后,由于燃烧的塑料滴落,无法从40厘米高的屏障阻止从上方蔓延的向下火势。该研究强调了水平防火屏障在防止垂直火蔓延至裸露的B2级聚苯乙烯绝缘材料上的局限性,并建立了进一步研究的方案。

著录项

  • 来源
    《Fire Technology》 |2016年第3期|649-662|共14页
  • 作者单位

    Chinese Peoples Armed Police Acad, Dept Fire Protect Engn, Langfang 065000, Hebei, Peoples R China;

    Chinese Peoples Armed Police Acad, Dept Fire Protect Engn, Langfang 065000, Hebei, Peoples R China;

    Chinese Peoples Armed Police Acad, Dept Fire Protect Engn, Langfang 065000, Hebei, Peoples R China;

    Chinese Peoples Armed Police Acad, Dept Fire Protect Engn, Langfang 065000, Hebei, Peoples R China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Expanded polystyrene foam; Extruded polystyrene foam; Exterior insulation; Fire barrier; Heat release rate;

    机译:膨胀聚苯乙烯泡沫;挤出聚苯乙烯泡沫;外墙外保温;防火;放热率;