Gaseous extinguishing systems are typically used in critical areas of a business that require protection from a developing fire situation, where water damage must be avoided. High risk areas such as computer/server rooms, electrical switchgear rooms, telecoms rooms as well as archive stores, laboratories, gas turbines and oil installations are just some of the applications in which these systems have been installed. The generic alarm sequence for gas extinguishing systems comprises four distinctive stages specified in British, European and international standards. The first stage indicates that a single detector has been activated and action is required. The second stage is identified by a pulsed tone and indicates that two detectors have been activated (known as the 'coincidence alarm') confirming the presence of a fire and the imminent release of the extinguishant system.
机译:气体灭火系统通常用于企业的关键区域,需要保护其免受正在发展的火灾情况的影响,在这种情况下必须避免水的损害。高风险区域,例如计算机/服务器室,电气开关柜室,电信室以及档案馆,实验室,燃气轮机和石油设施,只是其中已安装这些系统的部分应用程序。气体灭火系统的通用警报序列包括英国,欧洲和国际标准中指定的四个不同阶段。第一阶段表明已激活单个检测器,需要采取措施。第二阶段通过脉冲音来识别,并指示已激活两个检测器(称为“重合警报”),以确认有火和即将释放灭火系统。