首页> 外文期刊>IEE proceedings. Part C >High-voltage insulation co-ordination: timelags of parallel-plate, rod-plane, rod-rod gaps, cap and pin insulators and surge diverter
【24h】

High-voltage insulation co-ordination: timelags of parallel-plate, rod-plane, rod-rod gaps, cap and pin insulators and surge diverter

机译:高压绝缘配合:平行板,杆面,杆-杆间隙,盖和针式绝缘子以及浪涌分流器的时滞

获取原文
获取原文并翻译 | 示例
       

摘要

Percentage overvoltages against timelag characteristics show that, while for simulated lightning strokes a rod-rod gap, set to yield the same 50 percentage sparking voltage as a rod-plane gap, will protect it and cap and pin insulators for all magnitude of overvoltages, for a simulated switching surge a rod-rod gap is wholly inadequate. For complete protection, uniform field geometries like those produced by Rogowski profiled electrodes are required and this is almost achieved with surge diverters.
机译:相对于时滞特性的过电压百分比表明,尽管对于模拟雷击,杆-杆间隙(设置为产生与杆-平面间隙相同的50%的火花电压)将保护它以及帽盖和引脚绝缘子免受所有大小的过电压影响,例如模拟的开关喘振杆-杆间隙完全不足。为了获得完整的保护,需要像Rogowski异型电极那样产生均匀的场几何形状,而这几乎可以通过浪涌分流器来实现。