摘要

In power systems with appreciable resistance, the transformers already connected to the supply system can experience unexpected saturation during the inrush transient of an incoming transformer. This saturation, which is established by the asymmetrical voltage drop across the system resistance caused by the inrush current, demands offset magnetising currents of high magnitude in the already connected transformers. This generates a transient interaction between the transformers, a 'sympathetic interaction', that affects the magnitude and duration of the inrush current. As a consequence, problems in the operation of the system, such as false operation of transformer differential relays and prolonged temporary harmonic overvoltages, can occur. The sympathetic interaction between the transformers is analysed in the paper. System configurations with transformers in parallel and in series are investigated. The transformers and system models have been validated using small transformers.
机译:在具有明显电阻的电力系统中,已经连接到电源系统的变压器在输入变压器的浪涌瞬变期间可能会遇到意外的饱和。这种饱和是由浪涌电流引起的系统电阻两端的不对称电压降建立的,它要求在已连接的变压器中产生高幅度的偏置励磁电流。这会在变压器之间产生瞬态相互作用,即“同感相互作用”,从而影响浪涌电流的大小和持续时间。结果,可能会出现系统运行中的问题,例如变压器差动继电器的误操作以及长时间的临时谐波过电压。本文分析了变压器之间的同感相互作用。研究了并联和串联变压器的系统配置。变压器和系统模型已使用小型变压器进行了验证。