A pattern recognition method for localisation of the partial discharge (PD) site in an oil-filled transformer by acoustic measurements is presented. By dividing the transformer into a number of 20/spl times/20/spl times/20 mm/sup 3/ sub-modules, the PD site is localised by comparing the spatial distance of each sub-module to the acoustic sensors. The numerical cases indicate that the proposed method is general and practical, while avoiding some drawbacks in current algorithms. Moreover, the method improves the accuracy of localisation substantially when compared with the conventional localisation method.
机译:提出了一种通过声学测量来定位充油变压器局部放电(PD)部位的模式识别方法。通过将变压器分为20个/ spl次/ 20 / spl次/ 20 mm / sup 3 /个子模块,通过比较每个子模块与声学传感器的空间距离来定位PD位置。数值算例表明,该方法是通用且实用的,同时避免了现有算法的一些弊端。而且,与传统的定位方法相比,该方法大大提高了定位精度。