首页> 外文期刊>Energy >Experimental study on the heat exchange effectiveness of a dry coil indirect evaporation cooler under various operating conditions
【24h】

Experimental study on the heat exchange effectiveness of a dry coil indirect evaporation cooler under various operating conditions

机译:干式盘管间接蒸发冷却器在各种工况下热交换效率的实验研究

获取原文
获取原文并翻译 | 示例
           

摘要

In this study, a pilot Dry Coil IEC unit, an indirect evaporation cooler established by connecting a direct evaporation cooler and a sensible heat exchanger (SHE) in series, was made, and the effectiveness data of the pilot unit were acquired under various operation conditions in an environmental chamber realizing a wide-range of indoor and outdoor air conditions. The test result shows that over 40% effectiveness can be acquired even in hot and humid climates by using the Dry Coil IEC proposed in this paper. The Dry Coil IEC reduces the cooling coil size by pre-cooling the process air during the cooling season. It can also be used as an She reclaiming the sensible heat from the exhaust air during winter operation. The pilot unit recovered over 60% of sensible heat in the test. In addition, a simplified model of Dry Coil IEC returning the various operation conditions was developed based on existing models of an She and a direct evaporative cooler. A polynomial equation returning the effectiveness of the Dry Coil IEC was derived as a function of seven independent variables highly influencing the performance of the unit. The experimental data acquired by the pilot unit operation agree well with the effectiveness values of the Dry Coil IEC predicted by the proposed model. It was also identified that the proposed equation agrees well with the existing model of the Dry Coil IEC applied to the energy simulation program.
机译:在这项研究中,试制了干燥线圈IEC试点装置,这是通过将直接蒸发冷却器和显热交换器(SHE)串联连接而建立的间接蒸发冷却器,并获得了在各种运行条件下试点装置的有效性数据在一个环境室内实现广泛的室内和室外空气条件。测试结果表明,通过使用本文提出的干线圈IEC,即使在炎热和潮湿的气候下也可以获得40%以上的效率。 Dry Coil IEC通过在冷却季节对过程空气进行预冷却来减小冷却盘管的尺寸。在冬季运行期间,它还可以从废气中回收显热。在测试中,中试单元回收了超过60%的显热。此外,根据She和直接蒸发冷却器的现有模型,开发了返回各种运行条件的Dry Coil IEC简化模型。得出了返回干线圈IEC有效性的多项式方程,它是七个对单元性能有很大影响的独立变量的函数。通过试验单元操作获得的实验数据与所提出的模型预测的干线圈IEC的有效性值非常吻合。还可以确定,提出的公式与应用于能量模拟程序的干线圈IEC的现有模型非常吻合。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号