首页> 外文期刊>Energy >Experimental study on flame radiant heat flux from two heptane storage pools and its application to estimating safety distance
【24h】

Experimental study on flame radiant heat flux from two heptane storage pools and its application to estimating safety distance

机译:两庚烷储存池火焰辐射热通量的实验研究及其在估算安全距离中的应用

获取原文
获取原文并翻译 | 示例

摘要

This paper presents an experimental study on flame radiant heat fluxes from two identical pool fires in still air. The pool side length and spacing were changed. The fuel mass loss, flame height and radiative heat fluxes onto vertical targets far away from the fires were measured. A new method based on the weighted multi-point source model (WMP model) was developed to calculate the thermal radiation by determining the weight of each point source using the flame volume fraction. Results showed that both the SPS (single point source) and WMP models can well predict the radiative heat fluxes when the targets are located in the middle of two pools. For targets shifting from the centers of two pools, the SPS model will overestimate the radiative heat fluxes, while the accuracy of WMP model is much better. For the typical storage tank with 20 cm diameter, it is estimated that the heat flux received by the target located 30 m away from the edge of storage tank is 20.8 kW/m(2) using the proposed WMP model. And the acceptable safety distance of people (heat flux at the critical value of 1.4 kW/m(2)) exposed to the same storage tank fire is 166 m. (C) 2019 Elsevier Ltd. All rights reserved.
机译:本文介绍了静止空气中两种相同池火焰火焰辐射热通量的实验研究。池侧长度和间距被改变。测量燃料质量损失,火焰高度和辐射热通量在远离火灾的垂直目标上。开发了一种基于加权多点源模型(WMP模型)的新方法以通过使用火焰体积分数确定每个点源的重量来计算热辐射。结果表明,当目标位于两个池中时,SPS(单点源)和WMP型号都可以很好地预测辐射热通量。对于从两个池中的中心移位的目标,SPS模型将高估辐射热通量,而WMP模型的准确性好得多。对于直径为20厘米的典型储罐,估计使用所提出的WMP模型的距离储罐边缘30μm的目标接收的热量为20.8kW / m(2)。和人们的可接受的安全距离(临界值为1.4 kW / m(2)的热通量)暴露于同一储罐火灾量为166米。 (c)2019 Elsevier Ltd.保留所有权利。

著录项

  • 来源
    《Energy》 |2019年第1期|11-20|共10页
  • 作者单位

    Univ Sci & Technol China State Key Lab Fire Sci JinZhai Rd 96 Hefei 230026 Anhui Peoples R China;

    Univ Sci & Technol China State Key Lab Fire Sci JinZhai Rd 96 Hefei 230026 Anhui Peoples R China;

    Univ Sci & Technol China State Key Lab Fire Sci JinZhai Rd 96 Hefei 230026 Anhui Peoples R China|Univ Sci & Technol China Inst Adv Technol Hefei 230088 Anhui Peoples R China;

    Univ Sci & Technol China State Key Lab Fire Sci JinZhai Rd 96 Hefei 230026 Anhui Peoples R China;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Energy security; Multiple pool fires; Flame height; Multi-point source model; Radiative heat flux; Safety distance;

    机译:能源安全;多个池火;火焰高度;多点源模型;辐射热通量;安全距离;