首页> 外文期刊>Energy and Buildings >Outdoor synthetic temperature for the calculation of space heating load
【24h】

Outdoor synthetic temperature for the calculation of space heating load

机译:用于计算空间供暖负荷的室外合成温度

获取原文
获取原文并翻译 | 示例
           

摘要

Methods to select the outdoor design temperature (ODT) for heating load calculation specified in current design codes in different countries are firstly discussed. Then a new method namely Stochastic Analysis is presented to determine the outdoor synthetic temperature (OST), which fully considers the randomness of weather and internal casual gains, and the thermal performance of buildings. The concept of OST enables the design of space heating system to be the trade-off between economics and risk. Finally, case studies of the influence of different building components on OST of a residential room in Beijing have been studied, which shows that OST depends upon building structures as well as weather conditions. It is recommended that OST rather than ODT should be employed in heating load calculation hence, sizing equipment for space heating systems.
机译:首先讨论了在不同国家现行设计规范中指定的用于计算热负荷的室外设计温度(ODT)的选择方法。然后提出了一种新的方法,即随机分析法来确定室外综合温度(OST),该方法充分考虑了天气和内部临时收益的随机性以及建筑物的热性能。 OST的概念使空间供暖系统的设计成为经济与风险之间的权衡。最后,通过对不同建筑构件对北京某住宅房间OST影响的案例研究,表明OST取决于建筑结构和天气情况。建议在热负荷计算中使用OST而不是ODT,因此,应选择空间供暖系统的选型设备。