首页> 外文期刊>Energy and Buildings >Experimental study on partially internally cooled dehumidification in liquid desiccant air conditioning system
【24h】

Experimental study on partially internally cooled dehumidification in liquid desiccant air conditioning system

机译:液体干燥剂空调系统部分内部冷却除湿的实验研究

获取原文
获取原文并翻译 | 示例
           

摘要

The dehumidifier is one of the essential components in air-conditioning systems with liquid desiccant. Compared with adiabatic dehumidifiers, internally cooled dehumidifiers can achieve better dehumidification performance. In this study, dehumidification effectiveness and moisture removal rate were adopted to evaluate and compare the performance of these two kinds of dehumidifiers. The results indicated that internally cooled dehumidifiers can significantly improve performance compared with adiabatic dehumidifiers, especially when the solution is at a high temperature and/or low concentration in the downstream section of the liquid desiccant flow. Performance improvement and energy saving can be taken into consideration simultaneously by only supplying cooling water to the latter part of the dehumidifier. Solution temperatures at 20-25 C for adiabatic dehumidifiers are optimal and those at 25-30℃ for internal copied types. Lower temperatures of the cooling water can result in higher values for dehumidification effectiveness and moisture removal rate in an internally cooled dehumidifier; the limited temperature difference between cooling water and solution might seriously weaken the effect of the cooling water. Dimensionless Sherwood number Sh was calculated, and discrepancies between predicted values and experimental data are almost within ±20%.
机译:除湿机是带有液体干燥剂的空调系统的重要组成部分之一。与绝热除湿机相比,内部冷却的除湿机可以获得更好的除湿性能。在这项研究中,采用除湿效果和除湿率来评估和比较这两种除湿器的性能。结果表明,与绝热除湿器相比,内部冷却的除湿器可以显着提高性能,尤其是当溶液在液体干燥剂流的下游部分处于高温和/或低浓度时。通过仅向除湿机的后部供应冷却水,可以同时考虑性能改善和节能。绝热除湿机的最佳溶液温度为20-25℃,内部复制型的最佳温度为25-30℃。较低的冷却水温度可导致内部冷却的除湿机的除湿效率和除湿率更高。冷却水与溶液之间有限的温差可能会严重削弱冷却水的效果。计算了无因次舍伍德数Sh,预测值与实验数据之间的差异几乎在±20%之内。

著录项

  • 来源
    《Energy and Buildings》 |2013年第6期|202-209|共8页
  • 作者单位

    Department of Marine, Shanghai Maritime University, Shanghai 201306, PR China;

    Department of Marine, Shanghai Maritime University, Shanghai 201306, PR China;

    Department of Chemical and Biomolecular Engineering, National University of Singapore, 117576, Singapore;

    Department of Marine, Shanghai Maritime University, Shanghai 201306, PR China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Adiabatic; Partially internally cooled; Dehumidifier; Sherwood number Sh;

    机译:绝热的部分内部冷却;除湿机舍伍德数Sh;