The quasi-two stage compression air source heat pump (QTASHP) is still restricted in use in severe cold region due to the excessive discharge temperature caused by ultra-low ambient temperature. To promote the application of QTASHP in severe cold region, a novel control strategy was proposed, and it was used in a test rig in Harbin. The test rig adopted a scroll compressor with vapor injection, and its technical feasibility was investigated through supplying heating for a lab in the whole heating season. Then based on experimental results, its economic and environmental benefits were analyzed. Results showed that QTASHP could run smoothly in the whole heating season, and its highest discharge temperature was 118.82 degrees C at the highest compression ratio of 12.13. This indicated the proposed control strategy could solve the excessive discharge temperature problem effectively. Apart from ultra-low temperature, low temperature frosting was also a main challenge for QTASHP in severe cold region. Besides, comparing with central heating and electric boiler, its primary energy efficiency increased by 18.67% and 140.54%, while pollutants/CO2 emission decreased by 15.41% and 58.27%. However, its economic benefit was worse than central heating due to high initial investment, while far better than electric boiler. (C) 2020 Elsevier B.V. All rights reserved.
机译:由于超低环境温度引起的过度放电温度,Quasi-2级压缩空气源热泵(Qtashp)仍然限制在严重的冷区域中。为了促进Qtashp在严重的寒冷地区的应用,提出了一种新的控制策略,它在哈尔滨的试验室中使用。试验台采用具有蒸汽注入的涡旋式压缩机,通过在整个加热季节供应实验室的加热来研究其技术可行性。然后根据实验结果,分析了其经济和环境效益。结果表明,Qtashp可以在整个加热季节顺利运行,其最高放电温度为118.82℃,最高压缩比为12.13。这表明了所提出的控制策略可以有效地解决过多的放电温度问题。除了超低温度外,低温霜冻也是严重寒冷地区Qtashp的主要挑战。此外,与中央供暖和电锅炉相比,其主要能量效率增加了18.67%和140.54%,而污染物/二氧化碳排放减少了15.41%和58.27%。然而,由于初始投资的高初始投资,其经济效益比中央供暖更差,远远超过电锅炉。 (c)2020 Elsevier B.v.保留所有权利。

著录项

  • 来源
    《Energy and Buildings》 |2020年第9期|110152.1-110152.13|共13页
  • 作者单位

    Harbin Inst Technol Key Lab Cold Reg Urban & Rural Human Settlement E Minist Ind & Informat Technol Sch Architecture Harbin Peoples R China;

    Harbin Inst Technol Key Lab Cold Reg Urban & Rural Human Settlement E Minist Ind & Informat Technol Sch Architecture Harbin Peoples R China;

    Harbin Inst Technol Key Lab Cold Reg Urban & Rural Human Settlement E Minist Ind & Informat Technol Sch Architecture Harbin Peoples R China;

    Beijing Univ Technol Coll Architecture & Civil Engn Dept Bldg Environm & Facil Engn 100 Pingleyuan Beijing 100124 Peoples R China;

    Nanjing TICA Climate Solut CO Ltd Nanjing Peoples R China;

    Nanjing TICA Climate Solut CO Ltd Nanjing Peoples R China;

    Harbin Inst Technol Key Lab Cold Reg Urban & Rural Human Settlement E Minist Ind & Informat Technol Sch Architecture Harbin Peoples R China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Air source heat pump; Quasi-two stage compression; Severe cold region; Low temperature frosting; Seasonal coefficient of performance;