首页> 外文期刊>IEEE Transactions on Electromagnetic Compatibility >Analysis of Transient Performance of Grounding System Considering Frequency-Dependent Soil Parameters and Ionization
【24h】

Analysis of Transient Performance of Grounding System Considering Frequency-Dependent Soil Parameters and Ionization

机译:考虑频率依赖性土壤参数和电离的接地系统瞬态性能分析

获取原文
获取原文并翻译 | 示例
           

摘要

Frequency-domain approaches are usually used to study the impact of the frequency dependence of soil electrical parameters on the lightning response of grounding systems. On the other hand, time-domain simulations are required to study nonlinear soil ionization behavior. A time-domain frequency-dependent simulation is needed to incorporate both effects simultaneously. Based on dynamic harmonic domain (DHD) concept and transmission-line method, this paper derives a new approach for simulating the grounding system surge behavior that includes both time-dependent ionization and frequency-dependent effects of the soil. The DHD permits to decouple harmonic contents of each variable state during transients in time-domain simulation. The simulation results are validated against measured and simulated published results from other researchers. The comparison of experimental results and those provided by this model denoted its consistency.
机译:频域方法通常用于研究土壤电气参数频率依赖性对接地系统的雷电响应的影响。另一方面,需要时间域模拟来研究非线性土壤电离行为。需要一个时域频率依赖的模拟来同时整合两种效果。基于动态谐波域(DHD)概念和传输线方法,源于模拟接地系统浪涌行为的新方法,包括既有时间依赖性电离和土壤的频率依赖性影响。 DHD允许在时间域模拟中的瞬变期间耦合每个可变状态的谐波内容。模拟结果针对来自其他研究人员的测量和模拟发布结果验证。实验结果的比较和该模型提供的那些表示其一致性。