首页> 外文期刊>Electrical Engineers, Proceedings of the Institution of >Discriminative performance of distance protection under fault operating conditions
【24h】

Discriminative performance of distance protection under fault operating conditions

机译:故障操作条件下距离保护的判别性能

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

The paper is devoted to an evaluation in detail of the protection coverage afforded by earth- and phase-fault distance relays in terms of the range of apparent impedances presented to them for which the protection correctly operates and initiates circuit-breaker tripping. This requires a knowledge of both the effective polar characteristics of relays for specified system-fault conditions and also, for the same conditions, the apparent impedance to which the relays respond. Owing to the wide variation encountered in both of these in practice, the ordinary static characteristics of relays provide only a limited indication of the discriminative properties of distance relays in different applications, but it is shown how a comprehensive assessment may be made. In particular, investigations are described of the performance of mho relays when applied to 132kV and 400kV circuits, and the results of the investigations are summarised. The studies include the response to faults within the protected zone, the discrimination against external reverse faults, against healthy-phase relay operation and, on double-circuit-line constructions, the discrimination against healthy-circuit relay operation. The time response of comparators in impedance measurement is introduced, and it is explained how, evolving from this, the coverage afforded by the protection may be directly related to its operating time. In this way a basis is provided on which the operating time of distance relays may be systematically linked to its discriminative properties.
机译:本文专门针对提供给它们的视在阻抗范围,详细评估了接地故障和相故障距离继电器所提供的保护范围,为此保护可以正确运行并启动断路器跳闸。这要求既了解特定系统故障条件下继电器的有效极性特性,又要在相同条件下了解继电器响应的视在阻抗。由于在实践中这两种方法都存在很大的差异,因此继电器的普通静态特性仅能有限地表明距离继电器在不同应用中的区别性,但它显示了如何进行全面评估。特别是描述了对应用于132kV和400kV电路的Mho继电器的性能进行的研究,并总结了研究结果。这些研究包括对保护区内故障的响应,对外部反向故障的判别,对健康相继电器操作的判别,以及在双回线构造中对健康电路继电器操作的判别。介绍了比较器在阻抗测量中的时间响应,并由此解释了保护所提供的覆盖范围如何与其保护时间直接相关。这样就提供了一个基础,距离继电器的工作时间可以系统地与其区别性联系起来。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号