首页> 外文期刊>Electrical Engineers, Proceedings of the Institution of >Synthetic testing under short-line fault conditions. Comparison tests using an air-blast circuit breaker
【24h】

Synthetic testing under short-line fault conditions. Comparison tests using an air-blast circuit breaker

机译:短线故障条件下的综合测试。使用鼓风断路器的对比测试

获取原文
获取原文并翻译 | 示例
           

摘要

The paper is a contribution to work on the problem of synthetic testing under short-line fault conditions. Traditional `current-injection???????? circuits for terminal faults have already been extended to the case of the short-line fault by various authors. The circuit which is proposed in the paper accurately reproduces an actual short-line fault occurring in a network under most general conditions. The test circuit is described, and a survey is given on a complete series of tests carried out at CESI Laboratories, with the object of comparing synthetic and direct methods of testing. Test results have shown that the synthetic circuit adopted complies with the requirements for equivalence to the corresponding direct circuit. A confirmation of the results is given both by statistical analysis and by current-zero measurements, which allow a better insight into the interaction between test breaker and test circuit.
机译:本文为解决短线故障条件下的综合测试问题做出了贡献。传统的“电流注入”各种作者已经将终端故障的电路扩展到了短线故障的情况。本文提出的电路可以准确再现在大多数一般条件下网络中发生的实际短线故障。描述了测试电路,并对CESI实验室进行的一系列完整测试进行了调查,目的是比较综合测试方法和直接测试方法。测试结果表明,所采用的合成电路符合与相应直流电路等效的要求。统计分析和零电流测量都可以对结果进行确认,从而可以更好地了解测试断路器和测试电路之间的相互作用。