Transformer multiflow hottest-spot rating: proposed standard specification

机译:变压器多流最热等级:建议的标准规范

获取原文
           

摘要

The present practice in thermal rating is reviewed with recognition of its defects and limitations, of which the most serious is its inability to relate the standard rating with the hottest-spot temperature (h.s.t.). Modern improvements in cooling reduce the h.s.t., but are circumscribed by these limitations. The multiflow principle allows the h.s.t. to be determined for each individual winding from the present standard temperature-rise test measurements. It is anomalous that forced-oil cooling¿a standard rating for many years-has never been defined. It is quite legitimate to install such a small oil pump that the term has no real significance. The proposed international recognition of directed flow is neither justified nor desirable. Increased and directed flow are alternatives, and must both be recognised. In natural cooling, small distribution transformers are underrated and large ones are overrated. The h.s.t. multiflow rating removes all these anomalies, and leads to a draft revision of the present UK national standard rating for both natural and forced cooling. The proposed new rating can be determined as simply as the present standard rating but with the full benefit of the hottest-spot temperature limit controlling the thermal life of the insulation, and hence of the transformer itself. This benefit applies not only to the guaranteed rating but is available also for other service loading conditions of concern to the user. These sometimes bear little relation to the standard, but widen the practical field of application
机译:回顾了目前的热额定值实践,并认识到其缺陷和局限性,其中最严重的是无法将标准额定值与最热点温度(h.s.t.)联系起来。冷却方面的现代改进降低了h.s.t.,但受到这些限制的限制。多流原理允许h.s.t.根据当前的标准温升测试测量值,可以确定每个绕组的系数。多年来从未定义过强制油冷却的标准等级,这是异常的。安装这么小的油泵是完全合法的,因此该术语没有实际意义。提议的对定向流动的国际承认既没有正当理由也不可取。增加流量和定向流量是替代方法,必须同时识别两者。在自然冷却中,小型配电变压器被低估,大型配电变压器被高估。 h.s.t.多流额定值消除了所有这些异常现象,并导致对当前的英国自然冷却和强制冷却国家标准额定值进行了修订。可以像确定当前的标准额定值一样简单地确定建议的新额定值,但是可以充分利用最热点温度极限来控制绝缘的热寿命,从而可以控制变压器本身的热寿命。该好处不仅适用于保证的等级,而且还适用于用户关注的其他服务负载情况。这些有时与标准关系不大,但扩大了实际应用范围

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号