Continuing With Our Review Of The More significant 2002 NEC changes: 240.21(C)(6) This is a new tap rule allowing a 25-foot tap from a transformer secondary without overcurrent protection at the transformer end of the tap. The conductors shall have an ampacity that, when multiplied by the transformer secondary to primary voltage ratio, is at least one-third of the overcurrent protection rating on the transformer primary. They shall terminate in a single circuit breaker or set of fuses that limit the load current to not more than the conductor ampacity, and they shall be protected from physical damage.
机译:继续我们对2002年NEC的重大更改的回顾:240.21(C)(6)这是一条新的抽头规则,允许从变压器次级抽出25英尺的抽头,而在抽头的变压器端没有过电流保护。导体的载流量应乘以变压器的次级与初级电压之比,至少为变压器初级的过电流保护额定值的三分之一。它们应终止于单个断路器或一组熔断器,以将负载电流限制为不超过导体载流量,并且应保护它们免受物理损坏。