首页> 外文期刊>Electric power systems research >The voltage distortion in low-voltage networks caused by compact fluorescent lamps with electronic gear
【24h】

The voltage distortion in low-voltage networks caused by compact fluorescent lamps with electronic gear

机译:带电子齿轮的紧凑型荧光灯在低压网络中引起的电压失真

获取原文
获取原文并翻译 | 示例
           

摘要

Commonly used compact fluorescent lamps (CFLs) with electronic gear are characterized by extremely distorted current, with total harmonic distortion (THD) usually exceeding 100%. That is why they cause a significant voltage distortion in electrical installations. The principal goal of this research was to determine their maximum permissible share in the total load installed for commercial customers, at which voltage distortion is still acceptable (according to international standards). An analysis regarding a low-voltage electrical installation of a hotel, representing a typical commercial customer, showed that maximum permissible share should not exceed 10%. As this maximum permissible share could restrict the installment of the intended quantity of CFLs, the costs of two possible solutions for this problem - the use of filters or a new generation of CFLs with a high power factor - are compared.
机译:常用的带电子齿轮的紧凑型荧光灯(CFL)具有电流严重失真的特点,总谐波失真(THD)通常超过100%。因此,它们会在电气设备中引起明显的电压失真。这项研究的主要目的是确定在商业用户安装的总负载中其最大允许份额,在这种情况下电压失真仍然可以接受(根据国际标准)。关于代表典型商业客户的酒店低压电气设备的分析表明,最大允许份额不应超过10%。由于此最大允许份额可能会限制预期数量的CFL的安装,因此比较了解决此问题的两种可能解决方案的成本-使用滤波器或具有高功率因数的新一代CFL。