首页> 外文期刊>Electric power systems research >Performance assessment of distance protection fed by capacitor voltage transformer with electronic ferro-resonance suppression circuit
【24h】

Performance assessment of distance protection fed by capacitor voltage transformer with electronic ferro-resonance suppression circuit

机译:带有电子铁磁共振抑制电路的电容式变压器馈电距离保护的性能评估

获取原文
获取原文并翻译 | 示例
           

摘要

Distance relay may over-reach when the voltage information is delivered from capacitor voltage transformer (CVT) and when source to line reach impedance (SIR) is high. A technique adopted recently involves attacking the CVT transient problem from source side itself, i.e., by using electronic ferro-resonance suppression circuit (FSC), rather than allowing the transients and tackling this issue in the relay by providing adaptive zone 1 reach, providing a fixed time delay or using a narrow band pass filter which increases the total fault clearing time by the local relay. The work in this paper investigates the performance of CVT with electronic FSC for different fault, loading and SIR conditions.
机译:当从电容器电压互感器(CVT)传递电压信息时,并且当源到线到达阻抗(SIR)高时,距离继电器可能会超范围。最近采用的一种技术涉及从源侧本身解决CVT瞬态问题,即通过使用电子铁磁谐振抑制电路(FSC),而不是允许瞬态并通过提供自适应区域1到达来解决继电器中的这个问题,固定时间延迟或使用窄带通滤波器,这会增加本地继电器清除故障的总时间。本文的工作研究了带电子FSC的CVT在不同故障,负载和SIR条件下的性能。