Ferro-resonance over-voltage and power frequency over-voltage on the neutrals of 220kV power transformer and corresponding protection strategy

机译:220kV电力变压器中性点的铁磁过电压和工频过电压及其保护策略

获取原文

摘要

In order to limit short-circuit current and satisfy the need of relay setting, only part of the 220kV power transformer is grounded, so on the neutrals of ungrounded transformers will appear the over-voltage. Currently the value of over-voltage on transformer neutral point and the corresponding protection strategy is based on theoretical formula, this article use the PSCAD/EMTDC software to calculate the over-voltage on the neutral point of 4 ungrounded power transformers in Chongqing 220kV power grid, the result shows that the power frequency transient over-voltage on the neutrals may reach 178kV, If the single-phase grounding fault occurs in ungrounded power system, the power frequency over-voltage on the neutrals will be more serious and rise to 138.6kV. Non-full phase operation may cause serious ferro-resonance over-voltage on the neutrals of no-load transformer, which may last for seconds and may rise to 723.7kV, causing serious threat to the transformer neutrals and line-side equipment. The article also studies the gap parameter which should be taken on the neutrals of 220kV transformers at the end.
机译:为了限制短路电流并满足继电器设置的需要,仅220kV电力变压器的一部分接地,因此在未接地变压器的中性点上会出现过电压。目前变压器中性点过电压值及相应的保护策略是基于理论公式,本文使用PSCAD / EMTDC软件计算了重庆市220kV电网中4台不接地变压器的中性点过电压。结果表明,中性点上的工频瞬态过电压可能达到178kV,如果在不接地的电力系统中发生单相接地故障,则中性点上的工频过电压将更加严重,并上升到138.6kV。 。非全相运行可能会在空载变压器的中性线上造成严重的铁磁谐振过电压,这种过电压可能持续几秒钟,并可能升至723.7kV,从而对变压器中性线和线路侧设备造成严重威胁。本文还研究了最终应在220kV变压器的中性点上采用的间隙参数。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号