首页> 外文期刊>Electric power systems research >Influence of tertiary stabilizing windings on zero-sequence performance of three-phase three-legged YNynd transformers. Part I: Equivalent circuit models
【24h】

Influence of tertiary stabilizing windings on zero-sequence performance of three-phase three-legged YNynd transformers. Part I: Equivalent circuit models

机译:第三稳定绕组对三相三足YNynd变压器零序性能的影响。第一部分:等效电路模型

获取原文
获取原文并翻译 | 示例
           

摘要

The presence of a stabilizing winding (or tertiary stabilizing winding when is used to for auxiliary applications) in three-phase three-legged YNynd transformers remarkably affects the zero-sequence performance of both the transformer and the network. This paper presents a detailed analysis of the influence of the stabilizing winding on the zero-sequence behavior of three-phase three-legged YNynd transformers. Based on a complete set of onsite zero-sequence measurements taken in three power transformers, transformer zero-sequence performance is analyzed in relation to internal design features such as stabilizing winding position relative to high-voltage and low-voltage windings or the presence of magnetic shunts in the tank. Based on these measurements, this paper assesses the ability of various equivalent circuit models to reproduce zero-sequence performance accurately. A companion paper that complements this study evaluates the influence of stabilizing windings on tank overheating hazard and short-circuit duty in the event of asymmetrical faults. (C) 2016 Elsevier B.V. All rights reserved.
机译:三相三足式YNynd变压器中存在稳定绕组(或用于辅助应用时为第三稳定绕组)会显着影响变压器和电网的零序性能。本文详细分析了稳定绕组对三相三足式YNynd变压器零序行为的影响。基于在三台电力变压器中进行的一整套现场零序测量,结合内部设计特征(例如相对于高压和低压绕组稳定绕组位置或存在磁性)分析了变压器的零序性能。在坦克分​​流。基于这些测量,本文评估了各种等效电路模型准确再现零序性能的能力。补充本研究的另一篇论文评估了在出现非对称故障时,稳定绕组对储罐过热危险和短路负荷的影响。 (C)2016 Elsevier B.V.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号