A high-speed protection scheme for the DC transmission line of a MMC-HVDC grid

机译:MMC-HVDC电网的直流输电线路的高速保护方案

获取原文
获取原文并翻译 | 示例
           

摘要

High Voltage Direct Current (HVDC) grids based on Voltage-Source Converters (VSC) are flexible and can absorb large amounts of renewable energy. However, since the magnitude of fault current increases quickly, and it cannot be controlled after DC transmission line fault, the DC transmission line protection should operate very fast after the fault event. Otherwise, the DC circuit breakers will not be able to interrupt such a large fault current, which may cause permanent damage to the devices in the converter station. Based on the analysis of the feature of fault-induced travelling waves after DC transmission line fault, this paper proposes single-ended initial travelling wave based protection scheme. Based on the analysis of the feature of lightning disturbance, this paper also proposes fast identification scheme for lighting disturbance, in order to increase the reliability of the protection and maintain the high operation speed at the same time. A protection device prototype has been designed and implemented. Abundant tests have been conducted to verify the performance of the prototype device. The operation time of the protection is less than 1.2 ms.
机译:基于电压源转换器(VSC)的高压直流(HVDC)电网非常灵活,可以吸收大量可再生能源。但是,由于故障电流的大小会迅速增加,并且在直流输电线路发生故障后无法对其进行控制,因此在发生故障事件后,直流输电线路保护应非常快速地工作。否则,直流断路器将无法中断如此大的故障电流,这可能会对换流站中的设备造成永久性损坏。在分析直流输电线路故障后故障引起的行波特性的基础上,提出了基于单端初始行波的保护方案。在分析雷电干扰特征的基础上,提出了雷电干扰快速识别方案,以提高保护的可靠性,同时保持较高的运行速度。已经设计并实现了保护设备原型。已经进行了大量测试以验证原型设备的性能。保护的运行时间少于1.2 ms。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号